Product Description
The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).
The AS-Interface Master for the Anybus X-gateway implements an extended AS-Interface master (M4), and complies to version 3.0 of the AS-I Complete Specification.
It supports up to 62 slaves with a maximum of 248 digital input and 186 output signals. It also supports 124 analog values. All standard services are available including detailed diagnostics. The network interface is optically isolated and equipped with a 2-pin pluggable screw connector. The Master supports intelligent auto-configuration via the on-board configuration button or manual configuration via a terminal program such as Hyper Terminal for Windows.
The AS-interface module is certified by the AS Interface user organization and has proven conformance and interoperability with leading manufacturers of I/O, sensors, valves etc.
The Interbus 2Mbit/s interface module is a slave node that can be read from/written to by an Interbus master. Interbus has two ways of exchanging data; one through fast cyclical I/O data called ?Process Data?, and one through a somewhat slower protocol called PCP, which is mainly used for configuration purposes. It supports Interbus PCP V2.0. The module supports up to 10 words of data on the bus, out of which up to four words can be used for PCP.
Manages control of up to 62 AS-Interface slaves
248 digital inputs and 186 digital outputs
Intelligent auto configuration support
Individually isolated Bus In and Bus Out Interbus interfaces
Up to 10 words of Process data on Interbus
Interbus PCP v2.0 (0, 1, 2 or 4 words)
Supporting AS-Interface version 3.0
Size: 114 mm x 44 mm x 127 mm
Power Supply: 24 VDC (±20%)
Temperature: -25-65°C
Current Consump: max 400 mA
I/O Input: Default 20 bytes, max 64 bytes (248 digital inputs on ASI, max 20 bytes as I/O on Interbus)
I/O Output: Default 20 bytes, max 64 bytes (186 digital outputs on ASI, max 20 bytes as I/O on Interbus)
Mech Rating: IP20/Nema1
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
AS-I baudrate: 167 kbit/s
AS-I connector: 2 x 2-pole 5.08 mm Phoenix pluggable screw connectors
Interbus Baudrate: 500Kbit/s or 2Mbit/s
Interbus connectors: D-sub 9-pin ? Bus In male, Bus Out female
Price Group: C
Order Code: AB7825