AS-Interface Master – Profibus Slave

£602.00 ex. VAT

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

SKU: AB7821

Product Description

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The AS-Interface Master for the Anybus X-gateway implements an extended AS-Interface master (M4), and complies to version 3.0 of the AS-I Complete Specification.
It supports up to 62 slaves with a maximum of 248 digital input and 186 output signals. It also supports 124 analog values. All standard services are available including detailed diagnostics. The network interface is optically isolated and equipped with a 2-pin pluggable screw connector. The Master supports intelligent auto-configuration via the on-board configuration button or manual configuration via a terminal program such as Hyper Terminal for Windows.
The AS-interface module is certified by the AS Interface user organization and has proven conformance and interoperability with leading manufacturers of I/O, sensors, valves etc.

The Profibus DP/DPV1 slave interface is implemented according to the standard IEC61158 as a modular slave, supporting all standard functionality such as Watchdog, Sync and Freeze and diagnostics. Including I&M functions. Standard DP as well as DPV1 acyclic data services (Class1/Class2) are supported. The Profibus interface module is certified by the Profibus user organization and has proven conformance and interoperability with leading PLC´s, HMI´s etc. Profibus address is set via rotary switches 0-99.

Manages control of up to 62 AS-Interface slaves
248 digital inputs and 186 digital outputs
Intelligent auto configuration support
Watchdog support
Sync and Freeze
Supports PA baud rate 45.45 kbit/s
Complete Profibus DP and DPV1 (Class1/Class2) slave functionality according to IEC 61158
Supporting AS-Interface version 3.0

Size: 114 mm x 44 mm x 127 mm
Power Supply: 24 VDC (±20%)
Temperature: -25-65°C
Current Consump: max 400 mA
I/O Input: Default 20 bytes, max 64 bytes (248 digital inputs on ASI)
I/O Output: Default 20 bytes, max 64 bytes (186 digital outputs on ASI)
Mech Rating: IP20/Nema1
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
AS-I baudrate: 167 kbit/s
AS-I connector: 2 x 2-pole 5.08 mm Phoenix pluggable screw connectors
Profibus baudrate: 9600 bit/s – 12 Mbit/s autodetect
Profibus address ran: Node address 0-99
Profibus connector: D-sub 9-pin female
Profibus config.: Configured by Profibus Master via GSD file (provided by HMS)
Price Group: B