Ethernet/IP Adapter/Slave – CC Link Slave Industrial Network Gateway

£430.00

The Anybus Ethernet/IP Adapter/Slave – CC Link Slave Industrial Network Gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

SKU: AB7841

Product Description

The Anybus Ethernet/IP Adapter/Slave – CC Link Slave Industrial Network Gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Anybus OPC Server is supported and included with this X-gateway. It enables fast and dynamic transfer of fieldbus data to and from e.g. SCADA/HMI/Enterprice level systems based on Microsoft Windows.

The EtherNet/IP interface consists of an embedded 2-port Ethernet/IP 10/100 Mbit/s interface with IT functionality such as WEB-server, SSI-scripts, Flash file system, FTP-server, Email client, Telnet etc. It is possible to build web pages displaying and controlling a factory floor process with data from the other connected network. The EtherNet/IP interface module is certified by the ODVA and has proven conformance and interoperability with leading PLC´s, HMI´s etc. The dual port Ethernet interface will allow daisy chaning and removes the need for any external switch.

The CC-Link interface is a slave module for the CC-Link fieldbus system. It contains all the functionality needed to turn an application into a complete CC-Link remote device and it is configured to use the generic PLC profile. The CC-Link interface module is certified by the CLPA organisation and has proven conformance and interoperability with leading PLC´s, HMI´s etc 

 

 

Ethernet 10/100 Mbit/s twisted pair RJ45 connection
TCP/IP settings configurable with web-page, Configuration Tool, DHCP, ARP or with DIP switches
Ethernet/IP level 2 I/O Server CIP
1.4 Mbyte storage space on Flash disk
Support for AnyBus IPconfig utility for easy TCP/IP set up
SSI scripts used for easy display/control of process data on webpages
Gateway diagnostics via WEB-pages
Uses up to 4 occupied stations on CC-Link – configurable size
Uses the CC-Link PLC profile for data exchange
Support for CC-Link version 2.0 with extended data
Support for Anybus OPC Server

Size: 114 mm x 44 mm x 127 mm

Power Supply: 24 VDC (±20%)

Temperature: -25-65°C

Current Consump: Max 400mA at 24VDC

I/O Input: Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)

I/O Output: Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)

Mech Rating: IP20/Nema1

Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector

Ethernet/IP baudrate: 10/100 Mbit/s autodetect

Ethernet connector: RJ45

Ethernet/IP address: Any valid IP-address

Ethernet/IP config.: Configured by EtherNet/IP Scanner via EDS file (provided by HMS)

CC-Link baudrate: 156kbps to 10Mbps

CC-Link address: Station 1-64

CC-Link connector: 5-pole 5.08 mm Phoenix pluggable screw connector

CC-Link config.: Configured by CC Link Master via CSP Config file (provided by HMS)