Product Description
The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).
The FIPIO interface is based an embedded Anybus-S module providing industrial performance and quality. FIPIO station address can be selected via switches on the end side of the module. A transformer connection on the module provides a isolated fieldbus interface.
The CANopen interface is an adapter class product allowing fast data exchange. The CANopen slave?s data map consists of Process Data Objects (fast data) and Service Data Objects (slow data). The data on the CANopen bus is updated when a change is made or on request from another node. The CANopen interface module is certified by the Can In Automation organisation and has proven conformance and interoperability with leading PLC´s, SoftPLC´s, HMI´s etc
Supports both FIP and WorldFIP standards
FIPIO profile FEDP (Extended Device Profile), class 0
Transformer isolated FIP interface
CANopen PDO and SDO data objects supported
CANopen Unscheduled data exchange support
CANopen profile DS-301 v.4.02
Customizable PDO-mapping
Network Stor/Restore functionality
Heatbeat and node guarding support
Size: 114 mm x 44 mm x 127 mm
Power Supply: 24 VDC (±20%)
Temperature: -25-65°C
Current Consump: max 400 mA
I/O Input: Default 20 bytes, max 64 bytes
I/O Output: Default 20 bytes, max 64 bytes
Mech Rating: IP20/Nema1
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
FIPIO baudrate: 1 Mbit/s
FIPIO address: Node address 0-99
FIPIO connector: D-sub 9-pin male
CANopen baudrate: 10 kbit/s to 1 Mbit/s
CANopen connector: D-sub 9-pin male
CANopen address: Node address 1-99
CANopen config.: Configured by CanOpen Master via EDS file (provided by HMS)
Price Group: C
Order Code: AB7876