Product Description
The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).
The FIPIO interface is based an embedded Anybus-S module providing industrial performance and quality. FIPIO station address can be selected via switches on the end side of the module. A transformer connection on the module provides a isolated fieldbus interface.
The Modbus RTU Slave interface is implemented according to Modbus Protocol ref guide (PI-MBUS-300). All data is mapped to 3x and 4x Modbus areas meaning the Input Status and Output Register Word areas. The Modbus RTU standard baudrate is 19200 Bit/s but can be modified on the gateway between 1200 Bit/s to 57 600 Bit/s.
Supports both FIP and WorldFIP standards
FIPIO profile FEDP (Extended Device Profile), class 0
Transformer isolated FIP interface
Supported Modbus RTU functions: 1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23
Modbus RTU transmission media RS485
Size: 114 mm x 44 mm x 127 mm
Power Supply: 24 VDC (±20%)
Temperature: -25-65°C
Current Consump: max 400 mA
I/O Input: Default 20 bytes, max 64 bytes
I/O Output: Default 20 bytes, max 64 bytes
Mech Rating: IP20/Nema1
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
FIPIO baudrate: 1 Mbit/s
FIPIO address: Node address 0-99
FIPIO connector: D-sub 9-pin male
Modbus RTU baudrate: 1200 Bit/s to 57 600 Bit/s
Modbus RTU address: Node address 1-247
Modbus RTU connector: D-sub 9-pin female
Price Group: C
Order Code: AB7877