Modbus RTU Slave – CC Link Slave

£430.00

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

SKU: AB7621

Product Description

The Anybus X-gateway copies I/O-data in both directions thus enabling data exchange between the two networks. Default I/O configuration is 20 bytes Input and 20 bytes Output. Changing default settings is very easy using the windows based configuration software Anybus Configuration Manager X-gateway from HMS (free of charge).

The Modbus RTU Slave interface is implemented according to Modbus Protocol ref guide (PI-MBUS-300). All data is mapped to 3x and 4x Modbus areas meaning the Input Status and Output Register Word areas. The Modbus RTU standard baudrate is 19200 Bit/s but can be modified on the gateway between 1200 Bit/s to 57 600 Bit/s.

The CC-Link interface is a slave module for the CC-Link fieldbus system. It contains all the functionality needed to turn an application into a complete CC-Link remote device and it is configured to use the generic PLC profile. The CC-Link interface module is certified by the CLPA organisation and has proven conformance and interoperability with leading PLC´s, HMI´s etc

Supported Modbus RTU functions: 1, 2, 3, 4, 5, 6, 8, 15, 16, 22, 23
Uses up to 4 occupied stations on CC-Link – configurable size
Uses the CC-Link PLC profile for data exchange
Modbus RTU transmission media RS485
Support for CC-Link version 2.0 with extended data

Size: 114 mm x 44 mm x 127 mm
Power Supply: 24 VDC (±20%)
Temperature: -25-65°C
Current Consump: max 400 mA
I/O Input: Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)
I/O Output: Default 20 bytes, CC-Link V.2: max. 368 bytes (max 896 I/O-points and 128 words) CC-Link V.1: max 48 bytes (max 128 I/O-points and 16 words)
Mech Rating: IP20/Nema1
UL certification: E203225, Listed 67AM, UL-1604 Class 1, Div 2, GP A, B, C, D, Temp Code T4
ATEX certification: ATEX 135419, II 3 G, EEx nL IIC T4, DEMKO 03
Power supply connector: 2-pole 5.08 mm Phoenix pluggable screw connector
Modbus RTU baudrate: 1200 Bit/s to 57 600 Bit/s
Modbus RTU address: Node address 1-247
Modbus RTU connector: D-sub 9-pin female
CC-Link baudrate: 156kbps to 10Mbps
CC-Link address: Station 1-64
CC-Link connector: 5-pole 5.08 mm Phoenix pluggable screw connector
CC-Link config.: Configured by CC Link Master via CSP Config file (provided by HMS)
Price Group: A
Order Code: AB7621